Import guide · Côte d'Ivoire
Electrical standards in Côte d'Ivoire: 220 V, 50 Hz and type E sockets
Electrical equipment delivered to Côte d'Ivoire has to work on the local grid and pass the pre-shipment conformity check. These requirements overlap, because the Verification of Conformity (VoC) programme writes the expected voltage, frequency and plug type into its requirements.
For a European buyer this is fairly straightforward, as the values are close to those of continental Europe. It is less so for equipment designed for North America or some Asian markets, and for plugs fitted at the factory.
Updated on 20 October 2026
220 V and 50 Hz in the VoC datasheet
The VoC datasheet published by Bureau Veritas (revision 11.2, 02/2023) sets out the national deviations: mains-connected products must be rated 220 V, with 230 V accepted, and 50 Hz. European equipment marked 230 V and 50 Hz is therefore suitable without voltage conversion.
Frequency is the point to watch for equipment built for a different frequency, such as models intended for North America: motors, compressors, pumps and some internal clocks run at a different speed. An older CIE source notes that the national grid has to be held at around 50 Hz, a drop in frequency signalling that demand exceeds generation.
Sockets: French standard or a compliant adaptor
The VoC specifies French-type plugs and sockets under EN 50075, NF C 61-314 and NF C 61-315, together with type E (CEE 7). Other plug types may be accepted if supplied with a compliant adaptor.
In practice, a device ordered with a British or American plug should either be rewired at the factory or shipped with an adaptor meeting these standards. This belongs in the purchase order, not on the quayside.
What the conformity check also looks at
Electrical and electronic products, including renewable energy equipment, form one of the 13 categories covered by the VoC. Requirements draw on Ivorian, regional and international standards. The datasheet cites Decree No. 92-777 of 6 November 1992 on conduits for electrical installations and Decree No. 2016-1152 of 28 December 2016, which makes certain standards compulsory.
Analogue televisions and sets that do not meet broadcasting standards may not be imported. A training or communication project that includes screens should choose receivers according to the Ivorian broadcasting standard.
A wide grid with clearly defined players
According to the economy ministry's portal, installed capacity stood at 3,019 MW in 2024, with output of 13,919 GWh, 75.13% of it thermal. The network had 7,694 km of high-voltage lines, 34,656 km of medium-voltage and 32,433 km of low-voltage lines, and 98.6% of the population had access. The country exports power to Mali, Burkina Faso, Ghana and Liberia.
CIE, the concession holder, handles dispatching, transmission and distribution; CI-ENERGIES manages works; ANARE-CI regulates the sector. For a medium-voltage connection or an industrial installation, the exact supply characteristics should be confirmed with CIE.
How Sobetracom buys
Sobetracom states voltage, frequency and plug type in every request for quotation, rules out models not available in a 50 Hz version and checks that the conformity file covers the standards cited by the VoC. Technical requirements can change, so the buyer's licensed customs agent and the inspection company should confirm the rules in force before shipment.
Frequently asked questions
- Will a European 230 V appliance work in Côte d'Ivoire?
- On voltage, yes: the VoC requires 220 V and accepts 230 V, at 50 Hz. The plug still needs to be French type or type E, or come with a compliant adaptor.
- Can a pump designed for the North American market be imported?
- The VoC requires products rated for 50 Hz. A pump or motor built for another frequency risks being judged non-compliant and running poorly, so ask the manufacturer for a 50 Hz version.
- Are solar kits covered by the conformity check?
- Yes. The electrical and electronic category expressly includes renewable energy products.
Sources
- Bureau Veritas, fiche technique VoC Côte d'Ivoire, 02/2023, Rev. 11.2 (October 2026)
- Économie ivoirienne (portail du ministère de l'Économie), Électricité, page publiée le 26/11/2025 (October 2026)
- Abidjan.net / Nord-Sud, « Cie : au cœur de la production du courant », 11 janvier 2010 (October 2026)
This page summarises public sources as of the date shown. It does not replace the official text: check it before committing to a purchase, a bid or a shipment.