Equipment sourcing · Water and infrastructure
Submersible borehole pumps: specifying and buying for a water project in Africa
A submersible borehole pump runs tens of metres underground, often far from any workshop able to repair it. Selection mistakes are expensive: a motor that overheats for lack of cooling flow, impellers worn by sand, windings burnt by unstable voltage, or a borehole that runs dry because the pump draws more than the aquifer yields.
The tender should therefore start from the actual borehole and power supply rather than a catalogue. This page sets out what a public buyer or NGO can ask manufacturers for, drawing on the EU ecodesign regulation for water pumps, a borehole pump data booklet and the UNICEF and Water Mission design guide.
Updated on 20 October 2026
Start from the yield test
The duty point, flow and total head, comes from a pumping test on the borehole. The UNICEF and Water Mission guide is direct: a permanently installed oversized pump damages the aquifer and eventually itself, while an undersized one disappoints users. Because borehole yield often falls in the dry season, the test is best done at the least favourable time of year. Test procedures are set out in ISO 14686:2003.
Without a test report, quotes remain guesswork. The file sent to manufacturers should give borehole depth, static and dynamic water levels, casing internal diameter, delivery head to the tank and pipeline length.
Size, materials and water quality
Regulation (EU) No 547/2012 defines the submersible multistage borehole pump by its nominal diameter of 4″ (10,16 cm) or 6″ (15,24 cm) and a speed of 2 900 rpm. Casing bore decides the pump family: a 6″ motor will not go down a borehole built for 4″.
The manufacturer data booklet reviewed for this page shows what to compare between offers: AISI 304 stainless steel construction, built-in non-return valve, maximum sand content (150 g/m3 for the 4″ range, 300 g/m3 for the 6″ range) and maximum water temperature (35 °C for 4″ motors, 30 °C for 6″ motors). In sandy boreholes or aggressive water, these limits matter as much as efficiency.
Motor and power supply
In Africa the pump is often fed by an unstable grid, a generator or a solar inverter. The same booklet shows the values to require: 2-pole motor at 50 Hz, single-phase 230 V up to 2,2 kW in 4″, 3-phase 400 V above, voltage tolerance of ± 10 %. From 7.5 kW, the manufacturer requires star-delta, soft starter, stator impedance or autotransformer starting to limit inrush current.
Two limits shape operation. Water must flow past the motor at a minimum velocity (0,1 m/s for a 4″ motor, 0,5 m/s for a 6″ in this range); if the pump sits below the screens, a cooling shroud is needed. Starts are limited, here to 30 per hour in 4″ and 20 per hour in 6″, and repeated power cuts or a badly set level switch can reach that. The control panel should include dry-run, overvoltage and phase-loss protection, and any generator must be sized for starting.
Efficiency, installation and spares
For pumps placed on the EU market, Regulation 547/2012 has required since 1 January 2015 a minimum efficiency matching an MEI of 0,4, with a benchmark of MEI ≥ 0,70 for the best. The index and year of manufacture appear in the documentation, which helps compare offers from different origins on one basis.
Installation belongs in the purchase: rising main, drop cable sized for its length, waterproof splice, level probe, well cap with sanitary seal and a polypropylene or braided stainless safety line, as the UNICEF guide recommends, so the pump can be pulled without being lost. Order seals, an impeller set and a spare check valve.
From Belgium, Sobetracom consults several manufacturers using the test report and the available power source, compares curves at the same duty point and has conformity checked before dispatch. Relays in DR Congo, Burundi, Guinea and Nigeria follow acceptance on site; import rules should be confirmed with the licensed clearing agent.
Frequently asked questions
- 4 or 6 inch pump: who decides?
- The borehole. Casing bore and tested yield set the pump family; a 6″ motor will not fit casing built for 4″.
- Can a submersible pump run on a generator?
- Yes, if the generator is sized for starting current and the motor's voltage tolerance is respected, for example ± 10 % in the booklet reviewed. Above 7.5 kW, soft or star-delta starting limits inrush.
- Should the tender ask for an MEI value?
- For pumps made for the EU market, the MEI must appear in the documentation under Regulation 547/2012. Asking for it helps compare manufacturers from different countries.
Sources
- Règlement (UE) n° 547/2012 de la Commission, Journal officiel L 165 du 26.6.2012 (copie FAOLEX) (June 2012)
- Calpeda, catalogue 4SDP / 6SDP submersible borehole pumps 50 Hz (hébergé par Lenntech) (October 2026)
- UNICEF et Water Mission, Solar Powered Water Systems Design and Installation Guide (2020) (2020)
This page summarises public sources as of the date shown. It does not replace the official text: check it before committing to a purchase, a bid or a shipment.