Buying electrical cables for a project in Africa: standards, heat and inspection

Cables are often a large line item in an electrical project, and they hide the quality gaps that are hardest to spot: a copper cross-section slightly below the one printed on the sheath, insulation that cannot take the temperature, or a jacket that breaks down in the sun. The defect only shows in service, through overheating or voltage drop.

Sobetracom is not a cable maker. For ministries, utilities, NGOs and industrial buyers, we draft the specification from Belgium with the design office, approach manufacturers whose type tests can be verified, compare offers on the same designation and have lots inspected before shipment.

Updated on 21 October 2026

The conductor: what IEC 60228 guarantees

IEC 60228, now in its edition 4 of 2023, sets nominal cross-sections for power cable conductors from 0,5 mm2 to 3 500 mm2, along with wire numbers and sizes and, above all, the maximum resistance for each size. It covers solid, stranded and flexible conductors in copper and aluminium, and its requirements apply to the conductor in the finished cable.

Resistance is what protects the buyer: a cable sold as a given size but made with less metal will exceed the standard's maximum. Conductor resistance testing is simple, quick and telling, so we include it in the acceptance tests, sampling several drums from the lot.

Power cables: IEC 60502-1 and the full designation

For distribution networks and industrial installations, IEC 60502-1 covers extruded-insulation cables rated 1 kV and 3 kV: construction, dimensions and tests. It also states that a 1 kV cable may be used on DC, up to 750 V DC between live conductor and earth or 1 500 V DC between 2 live conductors, provided the manufacturer declares it. For a solar plant, that declaration should appear in the offer.

The specification should name the standard, the number and size of cores, the metal, the insulation (PVC or XLPE), any armour and the sheath. An offer that only gives a core count and a cross-section cannot be compared with anything. We ask for the manufacturer's type test reports and check that they cover the construction actually offered.

Heat changes the sizing

How much current a cable can carry depends on the temperature around it. IEC 60364-5-52, which deals with the selection and erection of wiring systems, uses a 30 °C reference for cables in air. Using the factors in its Table B.52.14, as reproduced by manufacturer VIOX, a PVC-insulated cable keeps only 0.87 of its rated current at 40 °C and 0.71 at 50 °C, while an XLPE cable keeps 0.91 and 0.82.

In a plant room under a metal roof or on a cable tray in full sun, those temperatures are routine. The design office therefore needs to size cables for the site's real temperature, and XLPE insulation, rated for a 90 °C conductor, is often justified. We make sure the selected offer matches that calculation rather than a table drawn up for a temperate climate.

Drums, marking and acceptance

Cable ships on drums whose weight and diameter decide the container, handling on arrival and pulling on site. We ask suppliers to state lengths per drum to limit joints, to seal cable ends against moisture and to mark the cable legibly along its length with maker, standard, designation and year.

On site, drums should be stored out of direct sun, which degrades some sheaths, and moved by rolling them in the marked direction or on a spindle, never by dropping them. Acceptance compares marking, lengths and lot test results with the order. Installation and approval rules specific to the destination country should be confirmed with the inspection body before purchase.

Frequently asked questions

Should we require testing by an independent laboratory?
For public or donor-funded contracts it is advisable, at least for conductor resistance and insulation dimensions, on samples taken from the delivered lot. The manufacturer's type test reports complement those checks but do not replace them.
Can a 1 kV cable be used on the DC side of a solar installation?
Under IEC 60502-1, a 1 kV cable may be used on DC within the limits set by the standard if the manufacturer declares it. Without that written declaration, a cable designed for the purpose is needed, and the design office decides.

Sources

  1. Standard Norge, fiche de la norme IEC 60228:2023 ED4 (October 2026)
  2. Standard Norge, fiche de la norme IEC 60502-1:2021 ED3 (October 2026)
  3. Standard Norge, fiche de la norme IEC 60364-5-52:2009 ED3 (October 2026)
  4. VIOX Electric, guide « Réduction de puissance électrique : température, altitude et facteurs de groupement » (fabricant) (October 2026)

This page summarises public sources as of the date shown. It does not replace the official text: check it before committing to a purchase, a bid or a shipment.