Sobetracom

Equipment sourcing · Raw materials

Buying water treatment chemicals for Africa: standards, shipping and storage

A water treatment plant or an emergency programme goes through tonnes of chemicals every month: coagulants such as aluminium sulphate, disinfectants such as calcium or sodium hypochlorite. A supply gap stops the production of safe water, and a degraded or impure product can compromise disinfection. Some of these products are also dangerous goods whose transport and storage in hot climates call for specific precautions.

Sobetracom is neither a chemical maker nor a distributor. For water utilities, WASH NGOs and donors, we draw up the specification from Belgium with the operator, approach manufacturers whose drinking-water compliance can be verified, compare offers on the same basis and arrange checks on the lot, the packaging and the transport documents.

Updated on 21 October 2026

Standards written for drinking water

An industrial chemical is not necessarily fit for drinking water treatment. In Europe each product has its own standard: EN 878 for aluminium sulphate, EN 900 for calcium hypochlorite and EN 901 for sodium hypochlorite. Each describes the product, sets requirements and test methods, and devotes an annex to safe handling. EN 901 adds that its impurity limits also apply to hypochlorite generated on site.

The specification should therefore name the product standard, the guaranteed active content and impurity limits, and require a certificate of analysis for each lot. We compare offers on those points and set aside any "technical grade" product offered without reference to drinking-water use.

Chlorine: a dose checked at the tap

How much disinfectant to buy follows from treatment targets. WHO Technical Note for Emergencies No. 11 gives simple benchmarks: turbidity below 5NTU and pH between 6.8 and 7.2 for chlorine to work well, at least 30 minutes of contact time, and residual chlorine of 0.2 to 0.5 mg/l where people collect their water. It also warns never to add solid chlorine directly to water but to make a paste first.

For the buyer, those figures have a direct consequence: consumption depends on raw water quality and network length. Order volumes are calculated with the operator from flow rates and measured chlorine demand, not from a flat estimate. Residual chlorine test kits belong in the same order.

Calcium hypochlorite is dangerous goods

Calcium hypochlorite is a Class 5.1 oxidiser. The P&I clubs' guidelines distinguish UN 1748, the dry form with more than 39% available chlorine, from UN 2880, the hydrated form containing 5.5% to 16% water. They explain that the product is always decomposing and releasing heat: if temperature rises and the heat cannot escape, the reaction runs away, and it has caused serious fires on board ships.

Packages must travel shaded from sunlight and heat sources, in ventilated spaces; in a reefer container the guidelines give a 10 °C set point. We confirm with the manufacturer and the forwarder the exact UN number, approved packaging, dangerous goods declaration and the shipping line's acceptance before the order is confirmed.

Sodium hypochlorite loses strength in the heat

Sodium hypochlorite starts losing chlorine as soon as it is made. According to manufacturer PAL International's technical sheet, a 15% solution decomposes 5 times faster at 45°C than at 25°C; light and metal impurities such as iron or copper also speed up breakdown, and the solution is most stable between pH 12 and 13. After weeks in transit through a hot climate, a concentrated solution can arrive well below its nominal strength.

The choice between calcium hypochlorite, delivered sodium hypochlorite and on-site generation is therefore made case by case, based on distance, available storage and consumption. We ask suppliers to guarantee strength on delivery rather than at production, and we plan quantities around short replenishment cycles.

Frequently asked questions

Is aluminium sulphate made for the paper industry suitable for a drinking water plant?
Not necessarily. For drinking water the product must meet EN 878, or the equivalent standard recognised in the country, including its impurity limits. A lot certificate of analysis checked against that standard is the evidence to ask for.
How should calcium hypochlorite be stored on a site without air conditioning?
In its original closed packaging, dry and shaded, away from combustible materials and heat sources, in a ventilated room. Stocks should be kept to what is actually needed, and national rules on storing oxidisers should be checked with the authorities of the destination country.

Sources

  1. Standard Norge, fiche de la norme NS-EN 878:2016 (October 2026)
  2. Standard Norge, fiche de la norme NS-EN 900:2014 (October 2026)
  3. Standard Norge, fiche de la norme NS-EN 901:2013 (October 2026)
  4. OMS / WEDC, Technical Note for Emergencies n° 11, « Measuring chlorine levels in water supplies » (October 2026)
  5. International Group of P&I Clubs et CINS, « Guidelines for the carriage of calcium hypochlorite in containers » (2018), publié par West P&I (2018)